Building Performance Modeling (BPM)

Application of Energy Modeling
Ansys Hall, Carnegie Mellon University
Instructor: Wei Liang
Master in Sustainable Design  |  Carnegie Mellon University, PA  |  2023
Tools: eQUEST, IESVE, Design Builder, & EnergyPlus
Type of Work: Team
Scroll Down

The BPM course focuses on conceptual foundations and practical applications of advanced and integrated whole-building energy simulation programs with emphasis on architectural building envelope systems, mechanical electrical building systems and their controls (electric lighting and HVAC systems) and building-integrated solar photo voltaic power systems. Building Information Modeling (BIM) concept and its connectivity to Building Energy Modeling (BIM).

The assignment aimed to familiarize me with the IES-VE 2021 software and analyze the energy performance of a specific building design case. By considering factors like site data, building materials, systems, operations, and loads, I gained insights into the synergistic impacts on energy efficiency during the design development phase. For this team project I worked on creating baseline building model, thermal templates & thermal zoning.

Baseline Model

Ansys Hall is a six story building located in Pittsburgh, PA. We used EnergyPlus (TMY3) weather data file for energy modeling using IES-VE. For construction of our baseline model we selected materials, which are compliant with requirements in the ASHRAE 90.1 2016 for climate zone 5A & created a baseline modeling following the outlines for building envelope, internal gains, & Operational schedules.

Baseline model outline

The above image represents the outline used to create the baseline model

NW elevation

NW elevation
Several areas of the building are connected to adjacent buildings, making it a complex design to model.

Solar Shading Analysis

In case of installing PV panels it is important to analyze the shading casted on the building by surrounding objects/vegetation, and energy received on each surface to leverage the maximum energy. 'Solar shading calculations' suggests that the roof and southern facade of the building receive maximum solar energy up to 300 - 437.23 kBtu/ ft2. Whereas the western facade receives the least due to adjacent buildings casting shadows.

Solar shading — SE elevation
Solar shading — top view

Solar shading analysis suggests that the roof and southern facade of the building receive maximum solar energy compared rest of the building.

Thermal Profile

Based on the types of usage and common thermal comfort requirements, we have created 14 thermal templates for Ansys Hall. Each template has a defined internal loads (refer a) and air exchanges (refer b) according to ASHRAE 62.1 - 2016 addendum for 'Ventilation for Acceptable Indoor Air Quality'.

No. Thermal Template Occupant Density (ft2 / person) Max Lighting Power Consumption (W / ft2) Max Computer Power Consumption (W / ft2)
1Baseline: Classroom/ Lecture/ Training - All Other15.381.41
2Baseline: Office - Open plan201.11.5
3Baseline: Office - Enclosed2001.11
4Baseline: Workshop501.90.22
5Baseline: Conference/ Meeting/ Multipurpose201.31
6Baseline: Computer Room111.832.1446.45
7Baseline: Lounge/ Breakroom401.21
8Baseline: Storage - >=50ft2—0.80.2
9Baseline: Storage - <50ft2—0.8—
10Baseline: Stairwell7500.6—
11Baseline: Restrooms7500.9—
12Baseline: Corridor - All Other Corridors7500.45—
13Baseline: Elevators - Equipment———

a. Baseline internal load (People, Lighting, Computer (Equipment)) values for each thermal template.

No. Thermal Template ASHRAE 62.1 Common Space Types Rp (cfm/person) Ra (cfm/ft2)
1Baseline: Classroom/ Lecture/ Training - All OtherLecture Classroom7.50.06
2Baseline: Office - Open planOffice Spaces50.06
3Baseline: Office - EnclosedOffice Spaces50.06
4Baseline: WorkshopLecture Hall (Fixed Seats)7.50.06
5Baseline: Conference/ Meeting/ MultipurposeConference/ Meeting50.06
6Baseline: Computer RoomComputer Lab100.12
7Baseline: Lounge/ Break roomBreak room50.12
8Baseline: Storage - >=50ft2Occupied storage rooms for dry materials50.06
9Baseline: Storage - <50ft2Corridors—0.06

b. Baseline Auxiliary Ventilation Values for each thermal template

IESVE chart 1 IESVE chart 2
Occupancy schedule 1 Occupancy schedule 2 Occupancy schedule 3

The default building office occupancy schedule was used with slight modifications.

Baseline Whole-Building Performance

Compared to median EUI per building type in the U.S., our baseline model for Ansys Hall have a relatively high EUI of 236 kBTU/sf.

EUI
(kBTU/sf/yr)
Electricity Usage
(MMBtu/yr)
Natural Gas Usage
(MMBtu/yr)
CO2 Emissions
(MT/yr)
Annual Energy Costs
($/yr)
236 839 3,221 204 $74,728

Parametric Analysis

Parametric analysis helped to reduce EUI of the building with emphasis on building envelope thermal properties, solar shading, occupancy features, and building geometric properties.

Parametric analysis diagram Key variables decreasing across iterations

All the key variables decreased during the iterations

Comparison of energy consumption — baseline vs final model

Comparison of Energy Consumption by End Use, Fuel Type, and Peak Usage

Conclusion & Recommendations

To prioritize retrofits and renovations in Ansys Hall, we recommend focusing on increasing insulation for the slab and improving the thermal properties of glazing, if feasible. Following a targeted approach to thermal zoning is recommended. Prioritizing HVAC and lighting upgrades in high-traffic areas such as classrooms and lounges, while implementing energy-saving measures like smart sensors in less frequently used spaces like corridors, can yield additional energy efficiency benefits.