The Environmental Performance Simulation (EPS) course provides an in-depth exploration of building
energy modeling, thermal analysis, and environmental simulation methods used in sustainable design.
Using parametric tools within Rhino and Grasshopper, the course equips students with computational
methods to evaluate and optimize building performance across multiple environmental criteria.
The project investigates Solar Radiation, Thermal Radiation, and Visible Radiation simulations to
understand the effects of surface orientation, glazing location, and building massing on occupant
comfort and energy consumption. Parametric studies using Climate Studio and the Ladybug Plugin were
conducted across annual, summer, and winter conditions to identify optimal design strategies.
Baseline Building Analysis: Solar Radiation Studies
Comparison of Total SED on different surfaces
Comparison of Total SED with different building orientations
Above comparison suggests roof followed by South facade received the most solar radiation.
Based on SED analysis we can propose the passive design strategies to reduce, eliminate,
or utilize the solar gain.
Above comparison suggests N-90 is giving lowest incident solar radiation. This study helps
understand the optimum orientation to reduce solar gain, thus heating & cooling loads
for the building.
Baseline Building Analysis: Thermal Radiation Studies
Hourly Temperature Analysis
The graph shows that indoor zone temp. is higher compared to site temp. due to internal
loads & lag in heat transfer caused by building envelope in the absence of HVAC system.
Spatial Thermal Comfort Analysis
The simulation output show distribution of Mean Radiant Temperature throughout the zone for open
office without HVAC. The results from MRT, PMV, & PPD suggest that on the coldest day (refer 1)
employees working near the glazing may experience a cooler environment compared to the north side,
whereas on the hottest (refer 2) employees seating near windows felt warmer compared to rest of the room.
1. Coldest day (Jan 08)
2. Hottest day (April 29) | HVAC Status | Date | Mean PMV | Mean PPD |
| OFF | Jan 8th, 06H | 1.53 | 52.4% |
| ON | Jan 8th, 06H | 1.66 | 58.3% |
| OFF | Apr 29th, 12H | 2.06 | 74.5% |
| ON | Apr 29th, 12H | 2.21 | 85.1% |
Summary of PMV & PPD for Open Office
Heat Loss & Heat Gain Analysis
The results of the heat loss & heat gain simulation have a direct relationship with the
occupancy of the building. Zone infiltration total heat gain energy and zone windows total
transmitted solar radiation energy is due presence of glazing.
Heat Loss for the Open Office on January 21
Heat Gain for the Open Office on July 21 Heating and Cooling Energy Consumption Analysis
The open office space uses more energy to cool the space than heat the space during all months
of the year. The conference room uses less energy to heat and cool the space due to lack of glazing.
Open Office
Closed Conference Room Whole-Building Environmental Performance Analysis
The "Load CS Energy Results" component is used to calculate the three metrics Whole Building
EUI, Carbon Emissions, and Operational Costs.
Site EUI (kWh/m2/yr) | Carbon Emissions (kgCO2/m2/yr) | Energy Cost ($/m2/yr) |
| 84.94 | 44.85 | 10.67 |
Proposed Design Measures: Improve HVAC Systems
To increase the efficiency of the mechanical system & reduce EUI without compromising with
occupant's thermal comfort we opted for three different 'Heat Pump Systems' options by increasing
their COPs & analyzed the 'Overall Building Performance'.
| Properties | Base case | HVAC -1 | HVAC -2 | HVAC -3 |
| System | Heat Pump | Air-Source Heat Pumps | Water Source Heat Pump | Ground Source Heat Pump |
| Heating System COP | 3.419 | 3.81 | 4 | 5 |
| Cooling System COP | 2.967 | 3.22 | 3.66 | 4.21 |
| Heat Recovery Ventilator (HRV) | OFF Type: Sensible | OFF Type: Sensible | OFF Type: Sensible | OFF Type: Sensible |
Variations of Heat Pump systems used compared to baseline system
Comparison of overall building performance for proposed iterations in HVAC systems with the baseline
| Performance | Base case | HVAC -1 | HVAC -2 | HVAC -3 |
| Site EUI (kWh/m2/yr) | 84.94 | 83.51 | 81.97 | 79.9 |
| CO2 Emission (kgCO2/m2/yr) | 44.85 | 44.09 | 43.28 | 42.19 |
| Energy Cost ($/m2/yr) | 10.67 | 10.48 | 10.29 | 10.03 |
| Comparison of Results | — | -1.60% | -3.50% | -5.93% |
Results suggests GSHP is the most suitable system for the building