The course explored architectural design strategies to enhance energy conservation and natural conditioning for improved human comfort across diverse climates by integrating comfort principles, heat flow, and local climate variables.
The course focused on the latest advancements in building energy conservation, passive heating and cooling technologies, and their integration into comprehensive design specifications. The objective of this project was to create a professional energy consultant's report outlining specific retrofit measures, including siting, massing, organization, enclosure detailing, opening control, and passive system integration.
Project Scope
For one assignment, I selected a 3-Bed & 2-Bath residence located in Torrance, California, housing a family of four. The detailed steps can be listed as follows:
- Performed site analysis including climate analysis through ClimateConsultant
- Analyzed existing building forms & organizations
- Studied building details & Peak+ Annual Heat Loss Calculations for heat loss
- Evaluated energy bills & systems for energy consumption study
- Conducted energy consumption analysis using REM/Rate for energy modeling
- Suggested strategies for passive heating & cooling along with improved outdoor living
Existing Building Construction Details
Section AA'
Section BB'
Plan (Left) & Sections (Right) representing Mechanically Heated Zones in the Home
Detail R-1 (Roof to wall Junction)
| No. | Roof Layer | R-value (Cavity) | R-value (Rafter) |
| 1 | Air film, outside | 0.17 | 0.17 |
| 2 | Asphalt Shingles | 0.44 | 0.44 |
| 3 | Roofing paper | 0.06 | 0.06 |
| 4 | Plywood sheathing, 3/4" thick | 0.94 | 0.94 |
| 5 | Polyisocyanurate, unfaced, Rigid Insulation, 2" thick (7/inch) | 14.00 | 14.00 |
| 6 | Plywood sheathing, 3/4" thick | 0.94 | 0.94 |
| 7 | Wooden rafters, 2x4" studs | n/a | 4.38 |
| 8 | Unfaced Fiberglass insulation, 8" thick (2.5/inch) | 20 | n/a |
| 9 | Gypsum board ceiling, 1/2" thick | 0.45 | 0.45 |
| 10 | Air film, inside, horizontal surface | 0.62 | 0.62 |
| Total R-value | 37.62 | 22 |
| Total area weighted R-value | 35.27 |
| U-value | 0.028 |
Total R-Value35.27
U-Value0.028
Detail W-1 (External wall assembly)
| No. | Wall Layer (W1) | R-value (Cavity) | R-value (Stud) |
| 1 | Air film, outside | 0.17 | 0.17 |
| 2 | Traditional cement stucco, 5/8" thick (0.20/inch) | 0.125 | 0.125 |
| 3 | Lath | n/a | n/a |
| 4 | Waterproof building paper | 0.06 | 0.06 |
| 5 | Rigid Insulation, 5/8" thick (5.6/inch) | 3.5 | 3.5 |
| 6 | Plywood Sheathing panels, 3/8" thick | 0.77 | 0.77 |
| 7 | Wooden stud, 2x6" | n/a | 6.88 |
| 8 | Fibreglass batt insulation, 6" thick (3.2/inch) | 19.20 | n/a |
| 9 | Gypsum Board, 5/8" thick | 0.56 | 0.56 |
| 10 | Air film, inside, vertical surface | 0.68 | 0.68 |
| Total R-value | 25.065 | 12.745 |
| Total area weighted R-value | 23.20 |
| U-value | 0.043 |
Total R-Value23.20
U-Value0.043
Detail G-1 (Window assembly)
| No. | Window Layer (G1) | R-value (Glass) | R-value (Mullion) |
| 1 | Air film, outside | 0.17 | 0.17 |
| Central Mullion, 1.5" thick (@R-value 2.64/inch) | n/a | 3.96 |
| 2 | Soft coated Low-e glass, 1/8" thick | 3.5 | n/a |
| 3 | Argon Layer, 3/4" thick (@R-Value = 5.2/inch) | 3.9 | n/a |
| 4 | Soft coated Low-e glass, 1/8" thick | 3.5 | n/a |
| 5 | Air film, inside, vertical surface | 0.68 | 0.68 |
| Total R-value | 11.75 | 4.81 |
| Total area weighted R-value | 10.70 |
| U-value | 0.093 |
Total R-Value10.70
U-Value0.093
Estimated Envelope Assembly Details for the Existing Home
Energy Consumption Analysis & Conclusion
| Members | Detail | U-value (Btu/hrft2°F) | Total Area (ft2) | Heat loss Coefficient UA (Btu/hr°F) |
| Walls | W1 | 0.043 | 3767 | 161.98 |
| Windows | G1 | 0.093 | 242.19 | 22.52 |
| Doors | D1 | 0.07 | 166.625 | 11.66 |
| D2 | 0.2 | 46.29 | 9.26 |
| D3 | 0.2 | 23.142 | 4.628 |
| Roofs | R1 | 0.028 | 1485.41 | 41.59 |
Floor (Slab on Grade) | F-value | Perimeter (ft.) | |
| F1 | 0.81 | 154.54 | 125.18 |
| Air Changes/hr | Heated Volume | Heat Capacity | Heat Loss Coefficient |
| Infiltration | ( Number of Air Changes ) x ( Heated Volume of the Building ) x (The Heat Capacity of Air ) | |
| 0.5 | 15,226 | 0.18 | 1,370.34 |
| Total Heat Loss Coefficient (Total UA) Btu/hr°F | 1,747.137 |
| Peak Heat Loss | Total UA x T (Design Indoor °F - Design Outdoor °F) | BTU/hr |
| ( 1,747.13) x [68 - 35] | 57,655.52 |
| Annual Heat Loss | ( Total UA ) x (24hrs) x (Annual Degree Days- HDD) | BTU |
| (1,747.14 ) x (24) x (1,274) | 53,420,552.64 |
| Heating Energy Index | ( Annual Heat Loss )/ Area in sq.ft. | BTU/ sq.ft/yr |
| (53,420,552.64)/1324 | 40,347.84 |
| (BTU/ sq.ft/yr) x (0.00315 US Metric) | kWh/m2/yr |
| (40,347.84 ) x (0.00315) | 127.095 |
Peak + Annual Heat Loss Calculation
Breakdown of Heat Loss Sources
Breakdown of Energy Consumption Sources
The provided pie chart (see reference a) illustrates that a significant proportion of heat loss occurs through infiltration, followed by flooring. Additionally, heating constitutes the main contributor to energy consumption (refer to b). Therefore, it is crucial to enhance the building's insulation, improve energy efficiency, and minimize energy usage.
Proposed Retrofit Strategies to Reduce Future Energy Consumption
| Recommendations | Purpose | Product | Reference Image | Cost Analysis | Payback Analysis |
| 1. | Caulking | Infiltration Reduction | Dynaflex Ultra 10.1 Oz Clear Advanced Exterior Sealant (DAP) | /dynaflexultra_app2_18211_6x6.jpg) | Cost/Unit: $6.98, No. of Units: 6,10 Total Cost: 111.58/- | Previous Infiltration UA: 1,370.34 Btu/hr°F New Infiltration UA: 1,096.28 Btu/hr°F Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,420/- Annual Money Saved: $604.80/- Payback: 2 months |
| Weatherstripping | Infiltration Reduction | MOPMS Draft Stopper Sweep, Door Weatherproofing Stripping | /416zBdMtk1L.jpg) | |
| 2. | Light Bulbs | Energy Efficiency | LED Bulbs | /Bulbs.jpg) | Cost/Unit: $5.23/- No. of Units: 2 Total Cost: $10.46/- | Previous Annual Energy: 1024 kWh (Lighting) New Annual Energy: 1,008.4 kWh Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,978/- Annual Money Saved: $46.00/- Payback: 2 months |
| 3. | Power Strip | Energy Efficiency | Trickle Star 7 Outlet Advanced Power Strip | /180ss_us_8xx_thumb_1__62147.1460402117.jpg) | Cost/Unit: $25.99/- No. of Units: 2 Total Cost: $52.00/- | Previous Annual Energy: 4600 kWh (Appliance) New Annual Energy: 2,392 kWh Annual Energy Saved: 2,208 kWh Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,472/- Annual Money Saved: (2,208) x (0.25)= $552/- Payback: 9 months |
| 4 | Thermostat | Energy Efficiency | Honeywell Home RTH8560D Touchscreen Thermostat | /513R9IkiPHS._AC_SL1500_.jpg) | Cost/Unit: $84.71 No. of Units: 1 Total Cost: $184.71 | Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,897/- Annual Money Saved: $127.00/- Payback: 1.5 year |
| 5. | Refrigerator | Energy Efficiency | Smart wi-fi Enabled French Door Counter-Depth Refrigerator | /Picture16.png) | Cost/Unit: $2,699.00/- No. of Units: 1 Total Cost: $2,699.00/- | Previous Annual Energy: 4600 kWh (Appliance) New Annual Energy: 3,935 kWh Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,828/- Annual Money Saved: $196.00/- Payback: 1.4 years |
| 6. | Washer | Energy + Water Reduction | 5.2 cu. ft. Smart Capable White Top Load Washing Machine with Extra Power Button | /white-maytag-top-load-washers-mvw7230hw-e1_600.webp) | Cost/Unit: $1,049.00/- No. of Units: 1 Total Cost: $1,049.00/- | Previous Monthly Use: 160 Gallons (Appliance) New Monthly Use: 95 Gallons Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,800/- Annual Money Saved: $7.00/- Payback: 1.5 years |
| 7. | Dryer | Energy + Water Reduction | Samsung Top Load Electric Dryer with Sensor Dry DVE50R5200W | /Picture8.png) | Cost/Unit: $777.00/- No. of Units: 1 Total Cost: $777.00/- | Previous Annual Energy: 4600 kWh (Appliance) New Annual Energy: 3,956 kWh Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $3,000/- Annual Money Saved: $14.00/- Payback: 5 years |
| 8. | Shower head | Water Reduction | High Sierra's All Metal 1.5 GPM High Efficiency Low Flow Shower head | /81Umm1w+VAS._AC_SL1500_.jpg) | Cost/Unit: $49.95/- No. of Units: 2 Total Cost: $99.99/- | Previous Monthly Use: 2400 Gallons New Monthly Use: 1440 Gallons Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,896/- Annual Money Saved: $128.00/- Payback: 1.1 years |
| 9. | Solar PV | On-site Energy Generation | SunPower 390-420W Residential A-Series Panels | /germany-solar.jpg) | Cost/Unit: $384.70/- Area covered: 120 sq. ft. No. of Panels: 12 Total Cost: $3,847/- | Previous Annual Energy: 5,624 kWh (Total) New Annual Energy: 2,067 kWh Annual Energy Produced: 3,557 kWh Previous Annual Energy Cost: $3,024/- New Annual Energy Cost: $2,161/- Annual Money Saved: $863.00/- Payback: 4 years |
Summary of Retrofits + Recommendations
Zero Energy
Home Reference
Home Existing
Homes
010203040 5060708090 100110120 130140150
Less
Energy More
Energy
Before adoption of
Retrofits & Recommendations
Zero Energy
Home Reference
Home Existing
Homes
010203040 5060708090 100110120 130140150
Less
Energy More
Energy
After adoption of
Retrofits & Recommendations
The above illustration suggests that this home stands on 65th level on the HERS© Performance Index, thus making it 35% more efficient than the standard house on the scale after adoption of retrofits & recommendations